Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 15/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GV2-M series Motor Protection Circuit Breakers are mainly used for the overload and short circuit protection in AC50/60HZ,up to 660V,0.1-80A power circuit ,as a full voltage starter to start and cut off the motor,under the AC3 load or for the overload and short circuit protection of the circuit and power equipment in the power distribution network. The product conforms standard IEC60947-2 IEC60947-4-1
Model NO.
|
Rated Current In(A)
|
Thermal Tripping setting range (A)
|
Magnetic tripping current (A)
|
GV2- M01
|
0.16
|
0.1-0.16
|
1.5
|
GV2- M02
|
0.25
|
0.16-1.25
|
2.4
|
GV2- M03
|
0.4
|
0.25-0.40
|
5
|
GV2- M04
|
0.63
|
0.4-0.63
|
8
|
GV2- M05
|
1
|
0.63-1
|
13
|
GV2- M06
|
1.6
|
1-1.6
|
22.5
|
GV2- M07
|
2.5
|
1.6-2.5
|
33.5
|
GV2- M08
|
4
|
2.5-4
|
51
|
GV2- M10
|
6.3
|
4-6.3
|
78
|
GV2- M14
|
10
|
6-10
|
138
|
GV2- M16
|
14
|
9-14
|
170
|
GV2- M20
|
18
|
13-18
|
223
|
GV2- M21
|
23
|
17-23
|
327
|
GV2- M22
|
25
|
20-25
|
327
|
GV2- M32
|
32
|
24-32
|
416
|
The rated power of three-phase electromtor controlled by breaker(GV2 motor circuit breaker)
Adjusting range of rated current (A) | Standard power of three-phase electromotor( KW) AC-3 50/60Hz | |||||
230/240V | 400V | 415V | 440V | 500V | 690V | |
0.1-0.16 | - | - | - | - | - | - |
0.16-0.25 | - | - | - | - | - | - |
0.25-0.4 | - | - | - | - | - | - |
0.4-0.63 | - | - | - | - | - | 0.37 |
0.63-1 | - | - | - | 0.37 | 0.37 | 0.55 |
1-1.6 | - | 0.37 | - | 0.55 | 0.75 | 1.1 |
1.6-2.5 | - | 0.75 | 0.75 | 1.1 | 1.1 | 1.5 |
2.5-4 | 0.37 | 1.5 | 1.5 | 1.5 | 2.2 | 3 |
4-6.3 | 0.75 | 2.2 | 2.2 | 3 | 3.7 | 4 |
6-10 | 1.1 | 4 | 4 | 4 | 5.5 | 7.5 |
9-14 | 2.2 | 5.5 | 5.5 | 7.5 | 7.8 | 9 |
13-18 | 3 | 7.5 | 9 | 9 | 9 | 11 |
17-23 | 4 | 11 | 11 | 11 | 11 | 15 |
20-25 | 5.5 | 11 | 11 | 11 | 11 | 18.5 |
24-32 | 5.5 | 15 | 15 | 15 | 18.5 | 23 |
The disjointing current commuting value of breaker in instantmagnetic field
Rated current In(A) | Adjusting range(A) | Disjointing current(A) |
0.16 | 0.1-0.16 | 1.5 |
0.25 | 0.16-0.25 | 2.4 |
0.4 | 0.25-0.4 | 5 |
0.63 | 0.4-0.63 | 8 |
1 | 0.63-1 | 13 |
1.6 | 1-1.6 | 22.5 |
2.5 | 1.6-2.5 | 33.5 |
4 | 2.5-4 | 51 |
6.3 | 4-6.3 | 8 |
10 | 6-10 | 138 |
14 | 9-14 | 170 |
18 | 13-18 | 223 |
23 | 17-23 | 327 |
25 | 20-25 | 327 |
32 | 24-32 | 416 |