| Customization: | Available |
|---|---|
| Electricity Type: | AC |
| Number of Pole: | 1-3 |
| Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
|---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
JR28-36 bimetallic thermal overload relay, 3P, AC 50/60Hz up to 690V, provides overload and phase loss protection for three-phase motors, pluggable with CJX2 series contactors, manual & auto rese
JR28-36 thermal overload relay is widely matched with CJX2-32 AC contactors for three-phase asynchronous motor protection. It adopts bimetallic strip principle with temperature compensation design, built-in phase loss protection. Equipped with adjustable current dial, trip indicator and test button. Two reset modes available: manual reset and automatic reset. It can be plug-mounted on contactor or independently installed on 35mm DIN rail. Flame retardant housing, reliable performance, compliant with IEC 60947-4-1. OEM service supported.
3-pole bimetallic thermal element
Overload + phase loss protection
Temperature compensation Manual / automatic reset optional
Trip indicator & test button
Plug-in fit for CJX2-32 contactor
Optional DIN rail standalone mounting
Rated voltage up to AC 690V, 50/60Hz
CE approved, flame retardant shell




This series of thermal relay can be used in the circuit of 50Hz or 60Hz,rated insulation
voltage 660V,rated current 0.1-96A for protecting the phase break when the electric motor is
overload. The relay has different mechanism and temperature compensation & can be
plugged in LC1-D series AC contactor.It is the most advanced thermal relay in the nineties in the world.
A.Fundamental parameter of the main circuit
(a).Rated insulation voltage 660V.
(b).Rated working current 25,36,93A separately.
(c).The regulator seal of rated setting current and setting.
(d).Current of the thermal component(see list 1)
B.Auxiliary Circuit
(a).There is one pair of NO/ and N/C contact with electric insulation.
(b).Rated insulation voltage 500V.
(c).Rated frequency 50-60Hz.
(d).Use group, rated working voltage ,appoint thermal current and rated current.
Motion Characteristic: Three-phase Balance Motion Time
| Application |
|
JR28 series thermal relay is suitable for using in the circuit rated voltage up to 660V, ratedcurrent 93A AC 50/ 60Hz, for over-current protection of AC motor. The relay has the differentialmechanism and temperature compensation and can plug in CJX2 series AC contactor. Theproduct conforms to IEC60947-4-1 stardand. |
| Motion Characteristic: Three-phase Balance Motion Time |
| No | Times of the setting current | Motion time | Start condition | Ambient temperature | ||
| 1 | 1.05 | >2h | Cold state | 20±5oC | ||
| 2 | 1.2 | <2h | Heat state(Following the No.1 test) | |||
| 3 | 1.5 | <4min | ||||
| 4 | 7.2 | 10A | 2s< Tp≤10s | ≤63A | Cold state | |
| 10 | 4s< Tp≤10s | >63A | ||||
| Phase-losing Motion Characteristic |
| No | Times of the setting current | Motion time | Start condition | Ambienttemperature | |
| Any two phases | Another phase | ||||
| 1 | 1.0 | 0.9 | >2h | Cold state | 20±5oC |
| 2 | 1.15 | 0 | <2h | Heat state(Following the No.1 test) | |
| Specification |
| Type | Number | Setting range (A) | For contactor |
| JR28-25 | 1301 | 0.1~0.16 | CJX2-09~32 |
| 1302 | 0.16~0.25 | CJX2-09~32 | |
| 1303 | 0.25~0.4 | CJX2-09~32 | |
| 1304 | 0.4~0.63 | CJX2-09~32 | |
| 1305 | 0.63~1 | CJX2-09~32 | |
| 1306 | 1~1.6 | CJX2-09~32 | |
| 1307 | 1.6~2.5 | CJX2-09~32 | |
| 1308 | 2.5~4 | CJX2-09~32 | |
| 1310 | 4~6 | CJX2-09~32 | |
| 1312 | 5.5~8 | CJX2-09~32 | |
| 1314 | 7~10 | CJX2-09~32 | |
| 1316 | 9~13 | CJX2-09~32 | |
| 1321 | 12~18 | CJX2-09~32 | |
| 1322 | 17~25 | CJX2-32 | |
| JR28-36 | 2353 | 23~32 | CJX2-09~32 |
| 2355 | 30~40 | CJX2-09~32 | |
| JR28-93 | 3322 | 17~25 | CJX2-09~32 |
| 3353 | 23~32 | CJX2-09~32 | |
| 3355 | 30~40 | CJX2-09~32 | |
| 3357 | 37~50 | CJX2-09~32 | |
| 3359 | 48~65 | CJX2-09~32 | |
| 3361 | 55~70 | CJX2-09~32 | |
| 3363 | 63~80 | CJX2-09~32 | |
| 3365 | 80~93 | CJX2-95 | |
| JR28-150 | 4365 | 80~104 | CJX2-95 |
| 4367 | 95~120 | CJX2-95~115 | |
| 4369 | 110~140 | CJX2-115 |
| Type | Number | Setting range (A) | For contactor |
| JR28-150 | 5369 | 90~150 | CJX2-150 |
| JR28-200 | F5357 | 30~50 | CJX2-F115~F185 |
| F5363 | 48~80 | CJX2-F115~F185 | |
| F5367 | 60~100 | CJX2-F115~F185 | |
| F5369 | 90~150 | CJX2-F115~F185 | |
| JR28-630 | F5371 | 132~220 | CJX2-F225~F265 |
| F7375 | 200~330 | CJX2-F225~F500 | |
| F7379 | 300~500 | CJX2-F225~F500 | |
| F7381 | 380~630 | CJX2-F400~F630 |
Dimension![]() |
Accessories![]() |
| Packaging Details: | Type Measure(cm) Qty/ctn Kgs/ctn JR28-25 (LR2-D13) 51.5*25.5*30.5 100 17 JR28-36 (LR2-D23) 44*39.7*24.3 75 20 JR28-93 (LR2-D33) 44*39.7*24.3 50 23 JR28-150 (LR2-D43) 44*39.7*24.3 50 23 |
|---|---|
| Delivery Detail: | 30 days depends with goods quantity |